The BK9103 Bus Coupler connects PROFINET IO with the modular, extendable electronic terminal blocks. One unit consists of one Bus Coupler, any number from 1 to 64 terminals (255 with K-bus extension) and one end terminal.
The Bus Couplers recognise the terminals to which they are connected, and perform the assignment of the inputs and outputs to the words of the process image automatically. The BK9103 Bus Coupler supports 10 Mbit/s and 100 Mbit/s Ethernet. Connection is through normal RJ 45 connectors. The IP address is set on the DIP switch (offset to a freely selectable start address). In networks with DHCP (a service for the allocation of the logical IP address to the physical node address [MAC-ID]) the Bus Coupler obtains its IP address from the DHCP server.
The BK9103 contains a 3-port switch. Two ports operate external on RJ 45 connectors and can be utilised. The I/O stations can thus be configured with a line topology instead of the classic star topology. In many applications this significantly reduces the wiring effort and the cabling costs. The maximum distance between two couplers is 100 m. Up to 20 BK9103 Bus Couplers are cascadable, so that a maximum line length of 2 km can be achieved.
PROFINET is the open Industrial Ethernet standard of the PNO (PROFIBUS User Organisation). Internationally established IT standards such as TCP/IP are used for communication. PROFINET IO describes the data exchange between controllers and field devices and can be used in standard Ethernet networks. Commercial switches are used for networking purposes.
The BK9103 Bus Coupler supports the operation of all Bus Terminal types.
The analog and multi-functional Bus Terminals can be adapted to each specific application using the KS2000 configuration set. Depending on the type, the analog Bus Terminals' registers contain temperature ranges, gain values and linearisation characteristics. With the KS2000, the required parameters can be set on a PC. The Bus Terminals store settings permanently and in a fail-safe manner.
Optionally, the Bus Terminals can also be controlled by the control system. Via function blocks (FBs), the programmable logic controller (PLC) or the Industrial PC (IPC) handle configuration of the complete periphery during the start-up phase. If required, the controller can upload the decentrally created configuration data in order to centrally manage and store this data. Therefore, new adjustments are not necessary in the event of replacement of a Bus Terminal. The controller carries out the desired setting automatically after switching on.
| System data | PROFINET | BK9103 |
|---|---|
| Number of I/O stations | only limited by IP addresses |
| Number of I/O points | depending on controller |
| Data transfer medium | 4 x 2 twisted pair copper cable; category 3 (10 Mbaud), category 5 (100 Mbaud) |
| Distance between stations | 100 m between hub/switch and Bus Coupler or between Bus Coupler and Bus Coupler |
| Data transfer rates | 10/100 Mbaud |
| Topology | line or star wiring |
| Cascading | up to 20 BK9103 or max. line length 2 km |
![]() |
![]() |
| Technical data | BK9103 |
|---|---|
| Number of Bus Terminals | 64 (255 with K-bus extension) |
| Max. number of bytes fieldbus | 512 byte input and 512 byte output |
| Digital peripheral signals | 512 inputs/outputs |
| Analog peripheral signals | 256 inputs/outputs |
| Protocol | PROFINET RT (Class B) |
| Configuration possibility | via KS2000 |
| Data transfer rates | 10/100 Mbaud, automatic recognition of the transmission rate |
| Bus interface | 2 x RJ 45 (2-channel switch) |
| Power supply | 24 V DC (-15 %/+20 %) |
| Input current | 70 mA + (total K-bus current)/4, 500 mA max. |
| Starting current | 2.5 x continuous current |
| Recommended fuse | ≤ 10 A |
| Current supply K-bus | 1,750 mA |
| Power contacts | 24 V DC max./10 A max. |
| Electrical isolation | 500 V (power contact/supply voltage/fieldbus) |
| Weight | approx. 170 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Approvals | CE, UL, Ex, GL |
![]() |
![]() |
| Accessories | |
|---|---|
| TwinCAT PROFINET IO Controller | licence for using the TwinCAT PROFINET IO Controller |
| KS2000 | configuration software for extended parameterisation |
| Cordsets | cordsets and connectors |
| FC90xx-00xx | PC Fieldbus Cards with PCI interface |
![]() |
![]() |
| Ordering information | Description |
|---|---|
| BK9103 | PROFINET Bus Coupler for up to 64 Bus Terminals (with integrated 2-channel switch) |
| BK9053 | PROFINET “Compact” Bus Coupler for up to 64 Bus Terminals (255 with K-bus extension) |
| CX8093 | PROFINET Embedded PC |
![]() |
![]() |
| System |
|
|---|---|
| PROFINET | For further PROFINET products please see the system overview. |
![]() |
![]() |