The KL3311 and KL3312 analog input terminals allow thermocouples to be connected directly. The Bus Terminal’s circuitry can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminals. The KL3311/KL3312 can also be used for mV measurement.
| Technical data | KL3311 | KL3312 |
|---|---|---|
| Number of inputs | 1 | 2 |
| Power supply | via the K-bus | |
| Thermocouple sensor types | types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement | |
| Connection method | 2-wire | |
| Measuring range | in the range defined in each case for the sensor (default setting: type K; -100…+1,370 °C); mV measurement: ±30 mV…±120 mV |
|
| Resolution | 0.1 °C per digit | |
| Conversion time | ~ 200 ms | ~ 250 ms |
| Wiring fail indication | yes | |
| Measuring error | < ±0.5 % (relative to full scale value) | |
| Electrical isolation | 500 V (K-bus/signal voltage) | |
| Current consumption power contacts | – (no power contacts) | |
| Current consumpt. K-bus | typ. 65 mA | |
| Bit width in the process image | input: 1 x 16 bit data (1 x 8 bit control/status optional) | input: 2 x 16 bit data (2 x 8 bit control/status optional) |
| Configuration | no address setting, configuration via Bus Coupler or controller | |
| Special features | electrically isolated | – |
| Weight | approx. 70 g | |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C | |
| Relative humidity | 95 %, no condensation | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 20/variable | |
| Approvals | CE, UL, Ex | |
![]() |
![]() |
![]() |
| Special terminals | |
|---|---|
| KL3312-0010 | type J |
| KL3312-0011 | type J in Siemens S5 format |
| KL3312-0012 | type L |
| KL3312-0013 | type L in Siemens S5 format |
| KL3312-0014 | type B |
| KL3312-0015 | type B in Siemens S5 format |
| KL3312-0016 | type E |
| KL3312-0017 | type E in Siemens S5 format |
| KL3312-0018 | type N |
| KL3312-0019 | type N in Siemens S5 format |
| KL3312-0020 | type R |
| KL3312-0021 | type R in Siemens S5 format |
| KL3312-0022 | type S |
| KL3312-0023 | type S in Siemens S5 format |
| KL3312-0024 | type T |
| KL3312-0025 | type T in Siemens S5 format |
| KL3312-0026 | type U |
| KL3312-0027 | type U in Siemens S5 format |
| KL3312-0028 | 0…120 mV measurement |
| KL3312-0029 | type K in Siemens S5 format |
| KL3312-0040 | expanded temperature range for type S and L type S: -50…+1,700 °C (as supplied type L: -100…+900 °C) |
| KL3312-0110 | type J, Fahrenheit scaling |
| KL3312-2000 | setting of reference junction temperature via process image, unit 1/256° C in a 16 bit word |
| KL3312-2100 | external reference point temperature specification via process image is possible, the unit is 1/256 °C in 16-bit format, fast conversion time 65 ms |