The KL9400 power supply unit terminal is used to refresh the K-bus. Data is exchanged between the Bus Coupler and Bus Terminal over the K-bus. Each Bus Terminal draws a certain amount of current from the K-bus (see “Current consumption K-bus” in the technical data). This current is fed into the K-bus by the relevant Bus Coupler’s power supply unit. The standard couplers (BKxx00, BCxx00) make 1.75 A available to the K-bus, while the “Economy” Couplers (BKxx10) and the “Low Cost” Couplers (LCxx00) provide 0.5 A. In configurations with a large number of Bus Terminals it is possible to use the KL9400 in order to supply an extra 2 A to the K-bus.
| Technical data | KL9400 | KS9400 |
|---|---|
| Input voltage | 24 V DC (-15 %/+20 %) |
| Output voltage | 5 V DC |
| Output current | 2 A for K-bus supply |
| Diagnostics | – |
| Current consumpt. K-bus | – |
| Power contacts | 24 V DC max./10 A max. |
| Short-circuit-proof | yes |
| Electrical isolation | – |
| Residual ripple | – |
| Weight | approx. 65 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals | CE, UL, Ex, GL |
![]() |
![]() |