The KL9528 power supply terminal generates a 30 V DC output voltage from the 24 V DC control voltage with high-frequency decoupling for the operation of an AS-Interface network. The output voltage is short-circuit-proof and is limited to a current of 1.25 A. The LEDs display the input and output voltage. There is no electrical isolation between the input voltage and the output voltage. The connection to the KL6201 AS-Interface master is established via plugs.
| Technical data | KL9528 | KS9528 |
|---|---|
| Input voltage | 21...28.8 V DC |
| Output voltage | 30 V DC (+5 %/- 5 %) |
| Output current | max. 1.25 A |
| Short circuit current | max. 1.3 A |
| Efficiency | approx. 95 % |
| Current load | – |
| Diagnostics | – |
| K-bus length | 2 inputs, 2 outputs |
| Current consumpt. K-bus | typ. 10 mA |
| Short-circuit-proof | yes, automatic restart |
| Insulation voltage input/output | none |
| Insulation voltage | 1,500 V AC constant load field/K-bus |
| Weight | approx. 150 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals | CE |
![]() |
![]() |
Product announcement |