Top view
Signal LED 1
Signal LED 2
Manual/automatic
operation (Output 1)
Manual/automatic
operation (Output 2)
Output 1
Output 2
KM2642, KM2652 | 2-channel relay module 230 V AC, 6 A, manual/automatic operation
The digital KM2642 and KM2652 output terminals have two independent relay change-over contacts, which can be used for switching mains current consumers. For each channel a switch enables selection between automatic, manual on, manual off. In automatic mode the logical state of an output bit switches the relay. For manual mode a 24 V supply is required for the Bus Coupler. The output state – for KM2652 also the state of the switch – can be read by the controller.
| Technical data |
KM2642 |
KM2652 |
| Number of outputs |
2 x change-over |
| Nominal voltage |
230 V AC (max. switching voltage 250 V AC) |
| Switching capacity max. |
1.5 kVA |
| Switching voltage max. |
250 V AC |
| Load type |
ohmic, inductive, lamp load |
| Max. output current |
6 A |
| Switching current |
6 A AC/4 A DC at 30 V DC |
| Minimum permitted load |
100 mA (12 V DC) |
| Lamp test, electronic ballast |
max. 10 A starting current |
| Current consumption power contacts |
– (no power contacts) |
| Current consumpt. K-bus |
typ. 130 mA |
| Contact material |
AgSnO2 |
| Bit width in the process image |
2 inputs (relay ON/OFF), 2 outputs |
4 inputs (status hand, auto, relay ON/OFF), 2 outputs |
| Operating cycles |
106 |
| Operating cycles mech. (min.) |
1 x 106 |
| Operating cycles electr. (min.) |
1 x 105 (3 A/250 V AC) |
| Configuration |
no address or configuration setting |
| Special features |
manual/automatic operation |
| Weight |
approx. 110 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Approvals |
CE |
 |
 |
 |
| Further manual operating terminals |
|
| KM1644 |
4-channel manual operation |
| KM2614 |
4-channel relay module 230 V AC, 16 A, potential-free change-over contact, with manual operation |
| KM4602 |
2-channel analog output terminal 0…10 V, manual/automatic operation |
 |
 |