The up/down counter counts binary pulses, and transmits the counter state, in an electrically isolated form, to the higher-level automation device. Optionally, the EL1512 EtherCAT Terminal can be set up as an up or down counter (16 bits). The EtherCAT Terminal contains two inputs that indicate their signal state by means of light emitting diodes. The EL1512 is particularly suitable for simple counting tasks, e.g. in connection with flow meters.
| Technical data | EL1512 | ES1512 |
|---|---|
| Connection technology | 2 up counters |
| Specification | EN 61131-2, type 1, “0”: < 5 V DC, “1” : > 15 V DC |
| Number of inputs | 2 |
| Nominal voltage | 24 V DC (-15 %/+20 %) |
| “0“ signal voltage | -3…+5 V (EN 61131-2, type 1) |
| “1“ signal voltage | 15…30 V (EN 61131-2, type 1) |
| Input current | typ. 3 mA (EN 61131-2, type 1) |
| Input filter | 10 µs |
| Counting frequency | max. 1 kHz |
| Distributed clocks | – |
| Current consumption power contacts | typ. 14 mA + load |
| Current consumption E-bus | typ. 130 mA |
| Counter depth | 32 bits |
| Electrical isolation | 500 V (E-bus/field potential) |
| Bit width in the process image | input/output: 16 bit data, 16 bit control/status |
| Configuration | no address setting, configuration via the EtherCAT master |
| Special features | 10 μs input filter |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals | CE, UL, Ex |
![]() |
![]() |