The EL3068 analog input terminal processes signals in the range between 0 and 10 V. The voltage is digitised with a resolution of 12 bits and is transmitted (electrically isolated) to the higher-level automation device. The EL3068 EtherCAT Terminal combines eight channels in one housing. The power contacts are connected through. The 0 V power contact is used as reference ground connection for the inputs. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.
| Technical data | EL3068 | ES3068 |
|---|---|
| Number of inputs | 8 (single-ended) |
| Power supply | via the E-bus |
| Technology | single-ended |
| Signal voltage | 0…10 V |
| Distributed clocks | – |
| Internal resistance | > 130 kΩ |
| Input filter limit frequency | 1 kHz |
| Conversion time | 1.25 ms default setting, configurable |
| Resolution | 12 bits (16 bits presentation, incl. sign) |
| Measuring error | < ±0.3 % (relative to full scale value) |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 130 mA |
| Dielectric strength | max. 30 V |
| Bit width in the process image | inputs: 32 byte |
| Special features | activatable FIR/IIR filters, limit value monitoring |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals | CE, UL, Ex |
![]() |
![]() |